Protectowire 2000 FireSystem Especificaciones Pagina 51

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 63
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 50
~48 ~
1ST
LAST
ELR
4.7K
1/2W
1ST
LAST
LAST
1ST
ALARM ENABLE INPUT #1
ALARM ENABLE INPUT #2
ALARM ENABLE INPUT #4
ALARM ENABLE INPUT #3
AUX. ALARM RELAY DRIVE
SPARE
SPARE
AUX. ALARM RELAY DRIVE
ALARM ENABLE INPUT #3
ALARM ENABLE INPUT #4
ALARM ENABLE INPUT #2
ALARM ENABLE INPUT #1
CLASS B CONFIGURATION
CLASS A CONFIGURATION
TE1
TE2
-) RETURN
-) OUT
(+) OUT
+) RETURN
TE2
TE1
0
20
19
16
15
11
11
15
19
20
10
1
F7
FUSE
1.5 AMP
3AG
AE-91
SILENCE SWITCH
UP
TEST SWITCH
ALARM
SILENCED
SHORT
OPEN
KA
%@D9?>L+M<1B=H@1>45B1B4
)(&*%$
The AE-91 Alarm Expander Card provides one alarm notification appliance circuit which may be wired in a Class A or Class B
configuration (NFPA styles X and Z or W and Y). The module plugs into an expander board (EB-91A) expansion slot and can be
factory programmed for general alarm activation or for selective activation by up to (4) individual detection zones.
%&(*%$
A reverse polarity supervisory current monitors the field loop integrity reporting any short or open in the circuit to the control
panel. When a fault condition occurs the respective LED (yellow) illuminates in conjunction with the system trouble LED and the
system trouble buzzer pulses. Once an alarm input is received, general alarm or individual pre-programmed zones, the circuit
polarity reverses and 24V FWR is supplied to the field output terminals. The Alarm LED illuminates indicating activation. By
pressing the “Silence” button the alarm notification appliance circuit may be silenced. Once the circuit is silenced, pressing the
system reset button “Sys. Rst.” will reset the circuit. If the circuit is not silenced, pressing the “Sys. Rst.” button will reset the con-
trol panel but the Alarm Expander will remain in an alarm state until its “Silence” button is pressed. When wired as a Class A cir-
cuit, all devices will be supplied power in the event of a single open condition in the field wiring. When wired as a Class B circuit,
only the devices before the open condition will be supplied with power. Devices beyond the open condition G9<<>?D operate. This
module is equipped with an “Alarm Test” button that will simulate an alarm output being received by the module.
H@1>45B?1B4
95<4*5B=9>1<C
<1B=H@1>45B1B4

9C@<1I&1>5<
<1B=,?<D175 24 V Full wave rectified (FWR)
<1B=EBB5>D 1 amp per circuit Maximum
)E@5BF9C?BIEBB5>D 0.002 amp maximum
<1B=(5<1I! P&B R10-E1-X4-V185
EC5 1.5 amp (3 AG)
Maximum (2) conductor copper feed cable resistance may not exceed
1 ohm (Reference DS-9066)
*Circuit current rating may be limited (reduced) depending on the power
requirements of the system. Reference the Installation Wiring Diagram
for the specific rating of each system