17
Mechanical Protection
Whenever the Detector comes within 6 feet
(1.8m) of the floor, it should be enclosed in con-
duit. This applies particularly to entry into manu-
al stations, control units, zone or end-of-line
junction boxes, and to all runs through floors.
SSppeecciiaall AApppplliiccaattiioonn
IInnssttaallllaattiioonnss
“Where a line-type detector is used in an
application other than open area protection,
the manufacturer’s installation instructions
shall be followed,” (NFPA 72-10). This section
of the manual is intended to provide general
guidance for installing Protectowire in several
special applications such as cable trays, con-
veyors, etc. Protectowire Linear Heat Detector
should typically be installed as shown in the
following diagrams with reference to the cor-
responding application.
Cable Trays
Figure 20 illustrates Protectowire Linear Heat
Detector installed in a sine wave pattern in a
cable tray. The Detector is run on top of all
power and control cables in a tray and is
Figure 20
42-48 in. (107-122cm)
FROM FLOOR OR AS
CODE REQUIRES
Figure 19 Detail at Manual Station
Figure 20A
Estimating chart and formulas
Width of cable tray Multiplier
4 ft. (1.2m) 1.75
3 ft. (.9m) 1.50
2 ft. (.6m) 1.25
1 ft. 6 in. (.5m) 1.15
Length of cable tray x multiplier = Length of Protectowire
Length of cable tray in feet ÷ 3 + 1 = Number of mounting clips
(Approx. 1.1 clips per meter of cable tray length + 1)
Model CC-2 Clip
Side rail