The following chart (Figure 27) shows that in a
freezer with an operating temperature of
-40°F (-40°C), and fasteners placed every 5 feet
(1.5m), the minimum sag between each set of
fasteners (as measured from the horizontal fas-
tening plane) should be 1.125 inches (2.8cm).
Tunnels
In vehicular tunnel applications, Protectowire
Linear Heat Detector is typically installed on the
ceiling directly over the roadway as illustrated in
Figures 28 and 28A. The systems design may be
further enhanced by installing Protectowire in
the cable racks and equipment rooms which
house control and power cables for the tunnels
ventilation, communication, and signaling equip-
ment. In cable runs, the Detector may be
installed at each rack level in direct contact with
the cables. Because the Detector is a cable, it will
easily follow tray runs, change levels, and cover
vertical cable risers.
Figure 28
Figure 27
5 ft. (1.5 m)
5 ft. (1.5 m)
5 ft. (1.5 m)
1 1/8 inch (2.8 cm)
5 ft. (1.5 m)
1 inch (2.5 cm)
7
/8 inch (2.25 cm)
3/4 inch (1.9 cm)
SAG
MINIMUM
Figure 28A
-40
o
F (-40
o
C)
-20
o
F (-29
o
C)
-0
o
F (-18
o
C)
+20
o
F (-7
o
C)