21
Refrigerated Storage Areas
When Protectowire Linear Heat Detector is
used in refrigerated storage or warehouse
applications as the initiating device for pre-
action sprinkler systems, Factory Mutual loca-
tion and spacing guidelines are generally rec-
ommended.
Figure 26 shows the FM acceptance criteria
for open area ceiling applications which
requires that the Detector be installed at a
spacing not exceeding the allowable ceiling
sprinkler spacing.
Rack detection systems should be installed
based upon the following criteria: For single
row and double row racks, one line of detec-
tion cable is needed at each in-rack sprinkler
level. Locate the Protectowire detection cable
in the longitudinal flue space and attach it to
the horizontal load beam at the sprinkler line
level as illustrated in Figures 26A and 26B.
For multiple-row racks, a line of detection
cable is needed for each in-rack sprinkler
line at each in-rack sprinkler level. Locate the
detection cable in each longitudinal flue
space and attach to the horizontal load
beams at the sprinkler branch line levels.
Installation Advisory - When Protectowire is
installed in refrigerated warehouses and
freezer applications, prior to chill-down, it is
important to provide adequate slack or “sag”
in the wire during the installation process in
order to avoid excessive stress on splicing
connections which may result in open circuit
trouble conditions. This built-in slack is
intended to compensate for the contraction
of the Detector core which occurs during the
reduction in temperature as the facility is
brought down to it’s subfreezing operating
temperature.
Figure 26B
Figure 26
Figure 26A