The NDS-91-16X Sixteen Zone Alarm Scanner identifies the zone number in conjunction with linear alarm point identification of a
PROTECTOWIRE heat sensitive cable detection zone. In the automatic (AUTO) scan mode this device continually steps through
all active (not bypassed) detection zones until an alarm input signal is received. Once received, the zone is identified and displayed
with the alarm point location for approximately six (6) seconds; then resumes scanning for additional zones in alarm. The scanner
may also be stopped at any zone and/or advanced manually. With expander modules the NDS-91-16X can scan up to a total of
forty-eight (48) PROTECTOWIRE zones.
%&(*%$
While functioning in a normal standby scan (AUTO) mode the decimal point in the lower right corner of the scanner display pulses
indicating proper operation.
• To interrupt scan and “lock-on” to an individual zone; toggle the mode switch to the “STOP” (center) position. The display will
show the current scanned zone.
• To manually step to a zone, place the mode switch to the “STOP” position and momentarily toggle the switch to the
“MANUAL” (down) position. Repeat until the display shows the desired zone number.
• To continually scan, toggle the mode switch to the “AUTO” (up) position. The display is normally inhibited during the
scanning process to minimize power consumption. To change the display status, place programming jumper (see illustration) to
“INHIBIT” or “ENABLE” position.
• To eliminate a zone from the scanning cycle, slide the corresponding dip switch (see illustration) to the “BYPASS” (ON)
position. To reinstate a bypassed zone, slide the dip switch to the “ACTIVE” (OFF) position.
• For meter calibration (OPTION A) see Option “A” page of this manual.
~ 32 ~
0%$"(#)$$(
)&"/))#"/
0%$"(#)$$(
(+*%(
9C@<1I>8929D E=@5B
#?45
)5<53D9?>
)G9D38
?>>53D?B
1D54
%ED@EDC
)31>
#?45
)G9D38
0?>5I@1CC)G9D385C
To bypass a scanned zone, slide
the corresponding dip switch to
the on position
0?>5
>@ED
)97>1<C
Current
Display Active
55mA @ 24VDC
Current
Display Blanked
37mA @ 24VDC
Scan Speed Approximately 16 Zones/Sec
"*("$%(#*%$