~ 35 ~
SUPERVISORY 1
SUPERVISORY 2
ELR-4.7K
1/2 W
)
9C@<1I
&1>5<
)95<4-9B9>7
%@D9?>LM)G9D38)E@5BF9C?BI1B4)
Terminations
on expander
board terminals
TE1 or TE2
)(&*%$
The supervisory card SC-91A provides two Class A/B alarm initiating supervisory circuits to recognize the activation of a normal-
ly open switches (tamper, low air, temperature, etc.) Each zone is equipped with individual alarm (yellow) and trouble (yellow)
LED’s for diagnostic ease. This card plugs into the second edge connector slot of the Main Board (MB-91A) and/or any Expander
Board module (EB-91A/M) slot.
Important:
jumper settings must be positioned as noted.
%&(*%$
Supervisory Alarm
- A shorted supervisory device will initiate a supervisory alarm mode of operation. The on-card “ALARM”
(yellow) indicator will light steady and the “SYSTEM TROUBLE/SUP” (yellow) indicator on the Control Card CC-91A will light
steady. The System trouble buzzer will sound and the common supervisory and common trouble contacts on the MB-91A will
transfer.
Trouble
- An open in the detection loop will initiate the circuit into a trouble condition and activate the trouble buzzer located on
the MB-91A. The respective zone “TROUBLE” (yellow) indicator as well as the “SYSTEM TROUBLE/SUP” indicator on the
CC-91A will activate
+#&()**$)
)>4931D?BC)G9D38)E@5BF9C?BI1B4
),1B91D9?>C
MJ1 & 2
Placed jumpers across JP1 & 2 terminals 2 & 3 circuits are
assigned for supervisory alarm condition.
MJ3 & 4 Jumpers are not installed
MJ5 thru 8
Jumpers must be installed across JP5 & JP6
MJ7 & MJ8 are not installed.
MJ9
Placed across JP9 terminals 2 & 3 to clear zone trouble indicators
during an alarm condition. Placed across terminals 1 & 2 to main-
tain trouble indications during alarm condition.
MJ10 & 11
JP10 & JP11 must always be installed for circuits assigned for
waterflow alarm
SC-91A Switch Supervisory zone card: Provides (2) Class A/B switch supervisory detection circuits.
SC-91ANL Switch Supervisory zone card: Provides (2) Class A/B non-latching switch supervisory detection circuits.
SI-91A Intrinsic Switch Supervisory zone card: Provides (2) Intrinsic Class B switch supervisory detection circuits.
ALARM Yellow-Alarm Switch Supervisory Zone alarm indicator: Activates with respect to each Switch Supervisory zone in alarm.
TROUBLE Yellow Zone trouble indicator: Activates in respect to each zone in TROUBLE condition