Provides two independent detection zones. Each zone is uniquely configured with two Class B initiating circuits along with signal
processing circuitry. The ZC-95 is specifically designed for use with Protectowire’s 3-wire, Model TRI, dual temperature Linear
Heat Detector. This card senses two alarm trip levels. The first is Pre-alarm (Low temp.) @ 155°F and the second is Alarm (High
temp.) @ 200°F. In addition to a common alarm output signal, there is an auxiliary Pre-alarm output signal and an auxiliary Cross
Temperature (similar to cross zoning) output signal provided by means of the on board logic circuit (Fig. 2).
Note: When employed with the Alarm Point Location Meter (Option “A”) the point of actuation for the Low Temp portion of the
TRI wire detector is read only.
&&""%(#&&(%,)/)*#)%$"/
0,1B91D9?>C
0?>DB?<)G9D385C
0>4931D?BC)D1>41B4*I@50?>51B4C
"*(")&*%$)
Inherent
Current
30 mA per card
Supervisory
Voltage
21.5 VDC
Supervisory
Current
4.5 mA per circuit
Maximum
Alarm current
35 mA per circuit
Current to
insure alarm
12 mA per circuit
Maximum
loop resistance
1000 ohms per circuit
LHD per zone 5000 ft Max.
LHD = Linear Heat Detector
ZC-95 Dual Temperature Zone Card: Provides (2) “TRI” wire compatatible Class B detection zones.
ZC-95M
Metered Dual Temperature Zone Card: Provides (2) “TRI” wire compatible Class B detection zones also
compatible with the Alarm Point Location Meter (Option “A”).
Meter SW.
ZONE 1
Meter read switch Zone #1: Press and hold to read distance (ft/m) to alarm actuation point of Protectowire zone
in alarm. See Option “A” - Protectowire Alarm Point Location Meter.
Meter SW.
ZONE 2
Meter read switch Zone #2: Press and hold to read distance (ft/m) to alarm actuation point of Protectowire zone
in alarm. See Option “A” - Protectowire Alarm Point Location Meter.
ALARM Red Zone alarm indicator: Activates in respect to each high temperature zone in ALARM condition.
TROUBLE Yellow Zone trouble indicator: Activates in respect to each high temperature zone in TROUBLE condition.
PRE-ALARM Red Pre-Alarm zone indicator: Activates in respect to each low temperature zone in ALARM condition.
TROUBLE Yellow Pre-Alarm zone trouble indicator: Activates in respect to each low temperature zone in trouble condition.